Imported thyristor of electric heating thyristor power regulator
Control signal input
Optional 4-20mA, 0-10mA, 0-5V, 0-10V, 1-5V, 2-10V, PWM;
Support manual potentiometer adjustment;
Support panel key control and other signal input.
control mode

Integrated technology of voltage regulation, phase shift and zero-crossing cycle power regulation can realize closed-loop control of constant current, constant voltage, constant power, double closed-loop three-phase rectifier DC power supply, electrolytic power supply, electroplating power supply
load
Load rated voltage range: 220V, 380V, 440V, 660V, 1140V
Applicable load type: all kinds of pure resistive load, all kinds of inductive load, IR infrared lamp and other loads. Various DC power supply, electrolytic power supply and electroplating power supply
Load connection mode: three-phase star neutral point is not connected to zero for 3S, three-phase star neutral point is connected to zero for 4S, three-phase triangle connection method for 3D, and three-phase internal triangle connection method for 6D
protection system
Fast melting protection, precision current transformer overcurrent protection, phase loss protection, overvoltage protection, overtemperature protection, etc
communication
Optional standard MODBUS RTU communication
Optional standard PROFIBUS DP communication
Cooling mode
10A-30A air cooling
50A-1200A air cooling

1000A-3000A air cooling or water cooling
Other detailed parameters
This series of power regulators adopts the original imported Siemens thyristor from Germany, supports multiple control signal types, supports MODBUS communication, integrates multiple protection and alarm systems, and realizes the precise regulation of load through the precise control of voltage, current and power. The product adopts high-speed microprocessor technology and advanced energy-saving algorithm to make the product more energy-saving and environmentally friendly.
Input impedance: 120 Ω (4-20mA input mode)
Slow start time range: adjustable range 0-60 seconds
Output voltage control range: 0-98% of input voltage
Adjust output resolution: 0.2 °
Three-phase trigger unbalance: ≤ 0.6 °
Phase discrimination: automatic discrimination of R-S-T three-phase voltage
Protection action time:<20ms
Relay contact capacity: 250V AC 2A
External voltage control function: voltage regulation (internal)/0-100%
Insulation impedance: 20 M Ω 500V DC
Insulator strength: 2000V AC for 1 minute (220V) 2500V AC for 1 minute (380V)
Material and external coating: cold-rolled steel plate and electrophoretic spraying
Current limit function: adjustment range 20-110%
Overcurrent protection system: electronic type protection
Author: Dekun Technology
Link: https://www.jianshu.com/p/9e88b1e5ce03
Source: brief book